CFW-09 - QUICK PARAMETER REFERENCE
9
QUICK PARAMETER REFERENCE, FAULT AND STATUS MESSAGES
Software: V4.4X
Application:
CFW-09 Model:
Serial Number:
Responsible:
Date: / / .
I. Parameters
Parameters Function Adjustable Range
Factory
Unit
User's
Page
Setting Setting
P000 Parameter Access 0 to 999 0 - 118
READ ONLY PARAMETERS P001 to P099
P001 Speed Reference 0.0 to P134 rpm 118
P002 Motor Speed 0.0 to P134 rpm 118
P003 Motor Current 0.0 to 2600 A (rms) 118
P004 DC Link Voltage 0.0 to 1235 V 119
P005 Motor Frequency 0.0 to 1020 Hz 119
P006 Inverter Status rdy - 119
run
Sub
Exy
P007 Motor Voltage 0 to 800 V 119
P009 Motor Torque 0.0 to 150.0 % 119
P010 Output Power 0.0 to 3276 kW 119
P012 Digital Inputs DI1 ... DI8 Status 0 = Inactive (Open) - 119
1 = Active (Closed)
P013 Digital and Relay Outputs DO1, DO2, 0 = Inactive (Dropped-out) - 120
RL1, RL2, and RL3 Status 1 = Active (Picked-up)
P014 Last Fault 0 to 71 - 121
P015 Second Previous Fault 0 to 71 - 121
P016 Third Previous Fault 0 to 71 - 121
P017 Fourth Previous Fault 0 to 71 - 121
P018 Analog Input AI1’ Value -100 to +100 % 121
P019 Analog Input AI2’ Value -100 to +100 % 121
P020 Analog Input AI3’ Value -100 to +100 % 121
P021 Analog Input AI4’ Value -100 to +100 % 121
P022 WEG Use - - 121
P023 Software Version V4.4X - 121
P024 A/D Conversion Value of AI4 -32768 to +32767 - 121
P025 A/D Conversion Value of Iv 0 to 1023 - 121
P026 A/D Conversion Value of Iw 0 to 1023 - 121
P027 AO1 Value 0.0 to 100 % 122
P028 AO2 Value 0.0 to 100 % 122
P029 AO3 Value -100 to +100 % 122
P030 AO4 Value -100 to +100 % 122
P040 PID Process Variable 0 to 100 % 122
P042 Powered Time 0 to 65535 h 122
P043 Enabled Time 0 to 6553.5 h 122
P044 kWh Counter 0 to 65535 kWh 123
coin