175
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Range
[Factory Setting]
Parameter Unit Description / Notes
Inverter
Parameters
User 1
P204 = 10
P265 to P269 (DIx) = 20
DIx = 24 V
DIx = 0 V
DIx = 24 V
- The functions JOG+ and JOG – are valid only for P202 = 3 and 4.
- The option Fieldbus sets the DI as a remote input for the Fieldbus system
and in order to become effective it must be read as any other
DI of the inverter.
Disable Flying Start: Put +24 V at the digital input to disable Flying
Start.
- The function Loads user via DIx, permits the memory selection of the
user 1 or 2, process similar to P204 = 7 and P204 = 8, but the user is
loaded from the transition of a DIx programmed for this function.
The memory of user 1 is loaded, when the DIx status changes from low
level to high level (transition from 0 V to 24 V) and P265 to P269 = 20,
provided the current parameter contents of the inverter have been
transferred previously to the parameter memory 1 (P204 = 10).
The memory of user 2 is loaded, when the DIx status changes from high
level to low level (transition from 24 V to 0 V) and P265 to P269 = 20,
provided the current parameter contents of the inverter have been
transferred previously to the parameter memory 2 (P204 = 11).
User 2
P204 = 11 DIx = 0 V
P265 to P269 (DIx) = 20
Figure 6.35 - Details about the operation of the function load user via DIx
NOTE!
Ensure that when using this function, the parameter sets (User
Memory 1 and 2) are totally compatible with the used installations
(motors, ON/OFF commands, etc.).
User memory cannot be loaded when motor is enabled.
When two different motor parameter sets are saved into the User
Memory1 and 2, respectively, set for each user the correct values
at the Parameters P156, P157 and P158.
When the function 'Parameter Setting Disable' is programmed and
the DIx input is +24 V, the parameters cannot be changed, independent
of the values that have been set at P000 and P200. When the Dix input
is set to 0 V, the parameter changing will be conditioned to the values
set at P000 and P200.