CHAPTER 3 - INSTALLATIONAND CONNECTION
Connection 4 - FWD Run / REV Run
Selection function FWD/REV.
Parameters to be programmed:
Set DI3 to FORWARD Run
P265 = 8
Set DI4 to REVERSE Run
P266 = 8
When the FWD Run / REV Run Function is programmed, the function is
always active, in both local and remote operation modes.
At the same time, the keys and remain inactive (even when P224 = 0
or P227 = 0)
The direction of rotation is defined automatically by the FWD Run / REV Run
commands.
Clockwise rotation for Forward and Counter Clockwise rotation for Reverse.
The speed reference can be from any source (as in Connection 3).
Figure 3.17 - XC1 (CC9) wiring for connection 4
Connector XC1
1 DI1
2 DI2
3 DI3
4 DI4
5 DI5
6 DI6
7 COM
8 COM
9 24 Vdc
10 GND
REV Run S2
FWD Run S1