Quick Reference of Parameters, Alarms and Faults
English
MW500 | 15
Param.
Description
Adjustable
Range
Factory
Setting
User
Setting
Properties Groups
P0296 Power Supply Rated Voltage 0 = 200 - 240 V
1 = 380 - 480 V
2 = 500 - 600 V
According to
inverter model
ro, cfg READ
P0297 Switching Frequency 1500 to 15000 Hz 4000 Hz
P0299 DC-Braking Start Time 0.0 to 15.0 s 0.0 s
P0300 DC-Braking Stop Time 0.0 to 15.0 s 0.0 s
P0301 DC-Braking Frequency 0.0 to 500.0 Hz 3.0 Hz
P0302 DC Braking Voltage 0.0 to 100.0 % 20.0 %
P0303 Skip Frequency 1 0.0 to 500.0 Hz 20.0 Hz
P0304 Skip Frequency 2 0.0 to 500.0 Hz 30.0 Hz
P0306 Skip Band 0.0 to 25.0 Hz 0.0 Hz
P0308 Serial Address 1 to 247 1 NET
P0310 Serial Baud Rate 0 = 9600 bits/s
1 = 19200 bits/s
2 = 38400 bits/s
1 NET
P0311 Serial Bytes Config. 0 = 8 bits, no, 1
1 = 8 bits, even, 1
2 = 8 bits, odd, 1
3 = 8 bits, no, 2
4 = 8 bits, even, 2
5 = 8 bits, odd, 2
1 NET
P0312 Serial Protocol (1)(2) 0 = HMIR (1)
1 = Reserved
2 = Modbus RTU (1)
3 = Reserved
4 = Reserved
5 = Reserved
6 = HMI(1) + Modbus
RTU (2)
7 = Modbus RTU (2)
2 cfg NET
P0313 Comm. Error Action 0 = Inactive
1 = Ramp Stop
2 = General Disab.
3 = Go to LOC
4 = LOC Keep Enab.
5 = Cause Fault
1 NET
P0314 Serial Watchdog 0.0 to 999.0 s 0.0 s NET
P0316 Serial Interf. Status 0 = Inactive
1 = Active
2 = Watchdog Error
NET
P0320 Flying Start/Ride-Through 0 = Inactive
1 = Flying Start (FS)
2 = FS and RT
3 = Ride-Through (RT)
0 cfg
P0331 Voltage Ramp 0.2 to 60.0 s 2.0 s
P0340 Auto-Reset Time 0 to 255 s 0 s
P0343 Fault Mask 0000h to FFFFh
Bit 0 = F0074
Bit 1 = F0048
Bit 2 = F0078
Bit 3 = F0079
Bit 4 = F0076
Bit 5 = F0179
Bit 6 to 15 = Reserved
0007h cfg
P0349 Ixt Alarm Level 70 to 100 % 85 % cfg